A step-down transformer connected to the main supply of 220 V is used to operate 11V,88W lamp. Calculate
- Voltage transformation ratio and
- Current in the primary
उत्तर
Given data:
Vp = 220 V, Ps = 88 W, Vs = 11 V
Transformation ratio K = `"V"_"s"/"V"_"p"`
K = `11/220 = 1/20 = 1 : 20 = 1/20`
Current in the primary Ip = ?
`"P"_"S" = "V"_"S" "I"_"S"`
`"I"_"S" = "P"_"S"/"V"_"S" = 88/11` = 8 A
`therefore "I"_"p"/"I"_"S" = "K"`
`"I"_"p" = "KI"_"S"`
`therefore "I"_"p" = 1/20 xx 8 = 2/5 = 0.4`
Ip = 0.4 A
APPEARS IN
संबंधित प्रश्न
Explain the construction and working of the transformer.
The following diagram in Fig. 10.44 shows a coil X connected to a sensitive centre –zero galvanometer G and a coil P connected to a battery through a switch S.
(a) Describe the observation when the switch S is (i) closed suddenly, (ii) then kept closed, (iii) finally opened.
(b) Name and state the law which explains the above observations.
The secondary windings of a transformer in which the voltage is stepped down are usually made of thicker wire than the primary. Explain why.
A transformer lowers e.m.f. 220 V to 12 volts. If the number of turns in primary are 8800, how many turns are in secondary coil?
Transformer works on ______.
In a transformer, the number of turns in the primary and the secondary are 410 and 1230 respectively. If the current in primary is 6A, then that in the secondary coil is
A 200V/120V step-down transformer of 90% efficiency is connected to an induction stove of resistance 40 Ω. Find the current drawn by the primary of the transformer.
A transformer is used ______
An iron rod is placed parallel to magnetic field of intensity 2000 Am-1. The magnetic flux through the rod is 6 × 10−4 Wb and its cross-sectional area is 3 cm2. The magnetic permeability of the rod in Wb A-1m-1 is ______.